44 — electricalc
®
Pro
GROuND CONDuCTOR WIRE SIZE
You can use single or multiple service entrance conductor(s) to nd
the grounding electrode conductor for AC systems. When using
multiple conductors, the ElectriCalc Pro uses the equivalent Circular
Mils to nd the Grounding electrode conductor (based on NEC
Table 250.66).
Find the Grounding electrode conductor Wire Size required when
2/0 is the largest 3-Phase 75°C Copper service-entrance conductor
being used. What is the equivalent Aluminum size? What is the
equivalent Circular Mils?
KEYSTROKE DISPLAY

0.
1. Enter Wire Size and nd Ground Wire Size:

GRND 4 CU WIRE SIZE
2. Find Aluminum size:
GRND 2 AL WIRE SIZE
3. Find Circular Mils:
CMIL 133,100. WIRE
4. Display NEC Table:
NEC 250.66
* Wire size can also be entered in Circular Mils (e.g.,

enters 133,100 CMILs and displays 4 GRND
Wire Size). If Wire Size is not entered using the
key, the
calculation will be based on the Wire Size stored in the
key.